Which gas flare do I need? Determining the right size
The right flare size determines whether your plant stays safe in an emergency – and whether you pay for capacity you never need. Three pieces of information get you to the right size.
1. The maximum gas flow
What counts is the largest gas flow the flare has to burn on its own – usually when all CHP units are down or gas injection fails. If you only know the CHP output, use the rule of thumb: 1 MW electrical corresponds to approx. 450–500 Nm³/h of biogas.
2. The methane content
The flare is designed according to firing capacity. At C-nox, the size corresponds directly to the firing capacity in MW: an NTV 2.0 burns 2,000 kW, which at 55 % methane is around 365 Nm³/h. If the methane content falls, the possible gas flow rises – below about 30 % methane a lean gas solution is required.
3. The application
- Emergency flare for biogas or sewage gas: verdeckte Niedertemperaturfackel NTV oder die preisbewusste offene LCN-O
- Continuous operation, landfill gas, strict emission requirements: high-temperature flare HTV above 1,000 °C
Reserve and burner circuits
Plan for about 10 % reserve. If the gas flow fluctuates widely, multiple burner circuits (up to 4 at C-nox) ensure that the flare burns stably even with little gas.
Try it out: Unser Flare Finder calculates the right size for you in seconds.