Praxiswissen zu Betrieb, Störungen und Wartung von Gasfackeln und Gasregelstrecken.

Lean gas at landfills: when the high-temperature flare no longer ignites

At many landfills, gas volume and methane content fall year after year. At some point the gas is no longer sufficient for a gas engine or a conventional high-temperature flare – but degassing must continue.

What the rules say

The German LAGA guidance BQS 10-1 “Landfill gas” (2026 edition) describes exactly this development and names processes for lean gas, such as lean gas flares, lean gas burners and thermal oxidation. Principle: the plant technology must be adapted to the gas volume and composition, and downtime must be minimised.

Typical solutions

  • Lean gas flare for low methane contents, sometimes with heat recovery
  • Adjusting the gas collection – sometimes the methane content rises again as a result
  • Temporary flare during the conversion
  • Wartungsvertrag, which is often awarded at the same time in current tenders

How to proceed

Measure gas volume and methane content over several weeks. On this basis, we design the right solution and support you through to acceptance.

Request a lean gas design

Replacing a flare without downtime: how to change your gas flare safely

Many flares at wastewater treatment plants, landfills and biogas plants are 15 to 30 years old. Replacement creates a critical gap: as long as the old flare has been dismantled and the new one is not yet in operation, the safety device is missing.

The solution: a temporary flare

A mobile flare on a trailer or skid is connected before dismantling and takes over until the new flare is running. The same applies to the refurbishment of gas holders or digesters and to longer CHP overhauls.

Procedure in five steps

  1. Survey: gas volume, methane content, pressure, connections
  2. Design the new flare – with suitable reserve and burner circuits from the outset
  3. Deliver, connect and commission the temporary flare
  4. Dismantle the old flare, install and commission the new flare
  5. Collect the temporary flare, documentation to operator and authority

Tip for tenders

Include the temporary flare as a separate item in the bill of quantities. This prevents change orders and discussions on site.

C-nox supplies the flare, temporary flare, commissioning and maintenance from a single source. Talk to us.

Which gas flare do I need? Determining the right size

The right flare size determines whether your plant stays safe in an emergency – and whether you pay for capacity you never need. Three pieces of information get you to the right size.

1. The maximum gas flow

What counts is the largest gas flow the flare has to burn on its own – usually when all CHP units are down or gas injection fails. If you only know the CHP output, use the rule of thumb: 1 MW electrical corresponds to approx. 450–500 Nm³/h of biogas.

2. The methane content

The flare is designed according to firing capacity. At C-nox, the size corresponds directly to the firing capacity in MW: an NTV 2.0 burns 2,000 kW, which at 55 % methane is around 365 Nm³/h. If the methane content falls, the possible gas flow rises – below about 30 % methane a lean gas solution is required.

3. The application

  • Emergency flare for biogas or sewage gas: verdeckte Niedertemperaturfackel NTV oder die preisbewusste offene LCN-O
  • Continuous operation, landfill gas, strict emission requirements: high-temperature flare HTV above 1,000 °C

Reserve and burner circuits

Plan for about 10 % reserve. If the gas flow fluctuates widely, multiple burner circuits (up to 4 at C-nox) ensure that the flare burns stably even with little gas.

Try it out: Unser Flare Finder calculates the right size for you in seconds.

Gas filter on the flare: when to change it – and why?

The gas filter is the first component of the gas train. It protects downstream fittings such as pressure regulators and safety shut-off valves from particles, rust and deposits – an important protection especially with biogas, sewage gas and landfill gas.

Safety note: Work on gas plants, gas trains and electrical components may only be carried out by competent, instructed persons in compliance with the operating manual, the risk assessment and the applicable regulations. This article replaces neither the manufacturer documentation nor an on-site inspection.

How to recognise a clogged filter

  • Rising differential pressure across the filter (if a differential pressure gauge is installed)
  • Gas pressure too low downstream of the filter, pressure switch faults
  • The flare no longer reaches its rated capacity

How often should it be changed?

There is no fixed interval for all plants – it depends on gas quality, throughput and operating hours. The manufacturer specifications in the operating manual are decisive. It has proven useful to check the filter at every maintenance and to document the differential pressure in the operating log. This way you recognise trends before a fault occurs.

Spare parts

For many filter housings there are matching filter inserts and spare parts packs with filter mat and seals. Important: always replace the housing seal as well and have the leak tightness checked afterwards.

Tip: do not forget wear parts

In the maintenance contract Premium a wear parts package with ignition electrode, filter and seals is already included – and in all packages you receive a discount on spare parts in the shop.

Stuck?

A CONTEC service technician will call you back – for all manufacturers, even without a maintenance contract.

Book telephone supportLet us find your spare partView maintenance contracts →

Pressure switches on the gas train: interpreting faults correctly

Pressure switches monitor on gas flares whether the gas pressure (and for forced-draught burners the air pressure) is within the permissible range. If a pressure switch trips, the control system prevents start-up or shuts the plant down.

Safety note: Work on gas plants, gas trains and electrical components may only be carried out by competent, instructed persons in compliance with the operating manual, the risk assessment and the applicable regulations. This article replaces neither the manufacturer documentation nor an on-site inspection.

Gas pressure switch min. and max.

The Low gas pressure switch (min.) reports insufficient inlet pressure – e.g. with an empty gas holder, clogged filter or closed shut-off valve. The high pressure switch (max.) responds when the pressure exceeds the set value, e.g. with a defective pressure regulator.

Air pressure switch

On flares with a combustion air blower, an air pressure switch checks whether the blower delivers sufficient air. Causes of tripping include dirty intake openings, a defective blower or leaking or kinked sensing lines.

Cause or defective switch?

In most cases the pressure switch reports correctly – the cause lies in the plant. Only if the pressure measurement and switching point do not match is the switch itself suspect. Settings may only be changed as specified in the plant documentation.

Getting a replacement

Note the complete type designation (e.g. GGW, LGW, DG) including pressure range and connection type. Unsure? Send us a photo of the type plate – we will identify the part for you.

Stuck?

A CONTEC service technician will call you back – for all manufacturers, even without a maintenance contract.

Book telephone supportLet us find your spare partView maintenance contracts →

Gas flare maintenance: what operators should know

Gas flares often only run when needed – during overhauls, faults in CHP units or gas upgrading, or with surplus gas. That is exactly when they must ignite reliably. Regular maintenance is therefore not optional but a prerequisite for safe and permit-compliant operation.

Safety note: Work on gas plants, gas trains and electrical components may only be carried out by competent, instructed persons in compliance with the operating manual, the risk assessment and the applicable regulations. This article replaces neither the manufacturer documentation nor an on-site inspection.

What maintenance includes

  • Visual and functional inspection of the entire flare and gas train
  • Inspection of ignition device, ignition electrode and pilot gas train
  • Functional test of flame monitoring and safety shut-off valves
  • Check of pressure switches and gas filters
  • Check of control system, messages and operating log
  • Maintenance report for your documentation

What operators can do themselves

Regular visual checks, keeping the operating log and watching messages belong in the hands of trained operating staff. Our operator instruction teaches exactly this knowledge – at our works or on site.

What the regulations say

For biogas plants in Germany, TRAS 120 and TA Luft mainly require that the flare starts automatically before the pressure relief device releases gas, that its operating times are recorded and that maintenance and inspections are documented in the operating log. In addition, there are periodic leak tests and expert inspections. The specific requirements differ by federal state or country – your permit is always decisive.

Practical tip

Because the flare often does not run for weeks, we recommend at least annual maintenance with a functional test of ignition, flame monitoring and safety shut-off valves – plus regular test runs by the operating staff.

Maintenance does not replace inspection obligations

Important: maintenance does not replace the legally required periodic inspections, e.g. under the German Industrial Safety Regulation, or official acceptance tests. Responsibility for safe operation remains with the operator.

Plannable with a maintenance contract

With a Wartungsvertrag appointments are scheduled automatically, response times are fixed and you receive discounts on spare parts – for C-nox flares and plants from other manufacturers.

Stuck?

A CONTEC service technician will call you back – for all manufacturers, even without a maintenance contract.

Book telephone supportLet us find your spare partView maintenance contracts →

UV sensor and flame monitor: recognising and rectifying faults

Flame monitoring is a central safety function of every gas flare: if it detects no flame, the safety shut-off valves close. That is intended – but becomes a problem when the monitoring no longer reliably detects an existing flame.

Safety note: Work on gas plants, gas trains and electrical components may only be carried out by competent, instructed persons in compliance with the operating manual, the risk assessment and the applicable regulations. This article replaces neither the manufacturer documentation nor an on-site inspection.

How UV monitoring works

Eine UV sensor detects the ultraviolet radiation of the flame and sends a signal to the flame monitor or burner control. If the signal falls below a limit value, a safety shutdown follows.

Typical symptoms

  • Lockout shortly after successful ignition
  • Sporadic flame failures, especially at partial load or in wind
  • Weak or fluctuating flame signal in the control system
  • Extraneous light or self-test fault at start-up

Common causes

Dirty sight glass: soot, dust or condensate attenuate the UV radiation. Incorrect alignment: the sensor no longer “sees” the flame root, e.g. after modifications. Ageing: UV tubes and sensors lose sensitivity over time. Electrical causes: moisture in connectors or damaged cables.

Replacement: what to look out for?

The replacement sensor must match the existing flame monitor or burner control . Note the complete type designation of both devices from the type plate. After replacement, a functional test of the flame monitoring by a competent person is required.

Stuck?

A CONTEC service technician will call you back – for all manufacturers, even without a maintenance contract.

Book telephone supportLet us find your spare partView maintenance contracts →

Gas flare does not ignite – the most common causes

Eine Gasfackel, die nicht zündet, ist mehr als ein Ärgernis: Überschussgas kann nicht sicher entsorgt werden, und je nach Anlage drohen Emissions- oder Betriebsprobleme. Meist steckt eine von wenigen typischen Ursachen dahinter.

Safety note: Work on gas plants, gas trains and electrical components may only be carried out by competent, instructed persons in compliance with the operating manual, the risk assessment and the applicable regulations. This article replaces neither the manufacturer documentation nor an on-site inspection.

1. Zündelektrode verschlissen oder verschmutzt

Die Zündelektrode sitzt direkt im heißen Bereich und ist ein klassisches Verschleißteil. Abgebrannte Spitzen, Ablagerungen oder ein falscher Elektrodenabstand führen dazu, dass kein kräftiger Zündfunke entsteht. Prüfen lassen: Zustand der Elektrode, Abstand laut Betriebsanleitung, Risse im Keramikisolator.

2. Zündtransformator oder Zündkabel defekt

Liefert der Zündtransformator keine ausreichende Hochspannung oder ist das Zündkabel beschädigt, bleibt der Funke aus oder schlägt an anderer Stelle über. Typisches Zeichen: Die Steuerung läuft die Zündsequenz durch, aber es ist kein Zündgeräusch zu hören.

3. Kein oder zu wenig Zündgas

Bei Fackeln mit Zündbrenner muss das Zündgasventil öffnen und der Zündgasdruck stimmen. Leere Propanflaschen, geschlossene Absperrhähne, ein verstellter Druckregler oder ein defektes Magnetventil sind häufige Ursachen.

4. Hauptgas fehlt oder Gasqualität schwankt

Liegt der Methangehalt zu niedrig oder fehlt der Vordruck, zündet zwar der Zündbrenner, die Hauptflamme stabilisiert sich aber nicht. Prüfen lassen: Gasdruck vor der Regelstrecke, Stellung der Absperrarmaturen, gas filter auf Verstopfung, Gasanalyse.

5. Flammenüberwachung erkennt die Flamme nicht

Brennt die Flamme kurz und die Anlage geht trotzdem auf Störung, liegt das Problem oft bei der UV sensor: verschmutztes Sichtglas, falsche Ausrichtung oder ein gealterter Sensor. Mehr dazu in unserem Beitrag zur UV-Flammenüberwachung.

Systematisch vorgehen

Notieren Sie die Störmeldung der Steuerung und den Zeitpunkt in der Zündsequenz, an dem die Anlage abbricht. Damit lässt sich die Ursache meist schnell eingrenzen – und wir können Ihnen am Telefon gezielt helfen oder das passende Ersatzteil nennen.

Stuck?

A CONTEC service technician will call you back – for all manufacturers, even without a maintenance contract.