UV sensor and flame monitor: recognising and rectifying faults

Flame monitoring is a central safety function of every gas flare: if it detects no flame, the safety shut-off valves close. That is intended – but becomes a problem when the monitoring no longer reliably detects an existing flame.

Safety note: Work on gas plants, gas trains and electrical components may only be carried out by competent, instructed persons in compliance with the operating manual, the risk assessment and the applicable regulations. This article replaces neither the manufacturer documentation nor an on-site inspection.

How UV monitoring works

Eine UV sensor detects the ultraviolet radiation of the flame and sends a signal to the flame monitor or burner control. If the signal falls below a limit value, a safety shutdown follows.

Typical symptoms

  • Lockout shortly after successful ignition
  • Sporadic flame failures, especially at partial load or in wind
  • Weak or fluctuating flame signal in the control system
  • Extraneous light or self-test fault at start-up

Common causes

Dirty sight glass: soot, dust or condensate attenuate the UV radiation. Incorrect alignment: the sensor no longer “sees” the flame root, e.g. after modifications. Ageing: UV tubes and sensors lose sensitivity over time. Electrical causes: moisture in connectors or damaged cables.

Replacement: what to look out for?

The replacement sensor must match the existing flame monitor or burner control . Note the complete type designation of both devices from the type plate. After replacement, a functional test of the flame monitoring by a competent person is required.

Stuck?

A CONTEC service technician will call you back – for all manufacturers, even without a maintenance contract.

Book telephone supportLet us find your spare partView maintenance contracts →

0 replies

Leave a Reply

Want to join the discussion?
Feel free to contribute!

Leave a Reply

Your email address will not be published. Required fields are marked *