Pressure switch DG50 UG-4
291,43 € (net 244,90 €)
incl. VAT plus shipping costs
- Delivery time: 1–3 working days (for stock items)
- Parcel shipping from Germany: €9.90
- Personal expert advice: +49 4321 85199-0
- With Wartungsvertrag 5–15 % cheaper
Not sure if the part fits? Photo of the type plate to service@c-nox.de – or Let us find your spare part →
The DG50 UG-4 is a adjustable gas and air pressure switch for monitoring overpressure, negative pressure and differential pressure in industrial firing, gas control and process plants. The switching pressure is set via a handwheel. The device is suitable for natural gas, LPG, air and biogas with a low H₂S content and has gold-plated switching contacts for high switching reliability.
Technical data
| Feature | Value |
|---|---|
| Type | DG50 UG-4 |
| Design | Diaphragm gas pressure switch |
| Setting range DG50 | 2.5–50 mbar |
| Max. inlet pressure DG50 | 500 mbar according to the series manual; observe the type plate |
| Contacts | Gold-plated, version G |
| Switching capacity AC (DG..G) | 5–250 V AC; 0.01–5 A at cos φ = 1 or 0.01–1 A at cos φ = 0.6 |
| Switching capacity DC (DG..G) | 5–48 V DC; 0.01–1 A |
| Connection / degree of protection | Screw terminals / IP65, version -4 |
| Medium and ambient temperature | −20 to +80 °C according to manufacturer conditions |
The details refer to the manufacturer operating manual DG..B, DG..U, edition 11.24. For the specific version, the type plate and plant documentation are decisive. The complete manual is linked below.
For selection, connection and operation of the DG50 UG-4, the manufacturer documents and the complete device version are decisive.
The permissible switching voltages and currents differ according to AC and DC voltage and load type. Please refer to the linked operating manual DG..B, DG..U.
Product features
- Gas pressure switch of the DG series
- Version U for monitoring overpressure, negative pressure and differential pressure according to manufacturer documentation
- Version G with gold-plated contacts
- Version -4 with screw terminals and degree of protection IP65
Applications
Monitoring of gas and air pressure on industrial plants. Suitability for your specific gas flare or burner system must be checked against the plant documentation and the manufacturer approvals.
Scope of delivery
For details of the supplied accessories and the exact device version, please contact us at service@c-nox.de. Please state article number 10138 and the type designation DG50 UG-4.
Technical data sheet
Manufacturer operating manual DG..B, DG..U (English, PDF)
Documentation for the series. Observe the details of the complete version of your device.
Only logged in customers who have purchased this product may leave a review.
Related products

Spare parts for industrial
gas and flare technology.
CONTEC GmbH & Co. KG
Haberstraße 23
24537 Neumünster
Germany









Reviews