DUNGS LGW 50 – air pressure switch
291,43 € (net 244,90 €)
incl. VAT plus shipping costs
- Delivery time: 1–3 working days (for stock items)
- Parcel shipping from Germany: €9.90
- Personal expert advice: +49 4321 85199-0
- With Wartungsvertrag 5–15 % cheaper
Not sure if the part fits? Photo of the type plate to service@c-nox.de – or Let us find your spare part →
The DUNGS LGW 50 is a adjustable air pressure switch for monitoring overpressure, negative pressure or differential pressure in air, flue gas and exhaust systems. It is used in burner, ventilation and air-conditioning technology and monitors the safe operation of blowers and air flows
Use in gas flares
The air pressure switch monitors whether the combustion air blower or compressor is actually delivering. If there is no pressure, the control does not release ignition or shuts down safely. This prevents gas from entering the combustion chamber without sufficient air or without delivery.
When to replace?
- Switching point drifts or can no longer be adjusted
- Diaphragm leaking, contacts worn
- Frequent “air pressure missing” fault messages despite the blower running
Service from the flare manufacturer
- Advice from our service technicians – we know the parts from everyday use on gas flares
- Not sure if the part fits? Send us a photo of the type plate and we will check it free of charge.
- Installation, adjustment and functional test by C-nox technicians on request
Additional information
| Weight | 1 kg |
|---|
Technical data
Technical data
| Feature | Value |
|---|---|
| Type | LGW 50 A2 |
| Setting range | 2.5 … 50 mbar |
| Max. operating pressure | 500 mbar (50 kPa) |
| Switching differential | ≤ 1 mbar |
| Medium | Air, flue gases, exhaust gases and non-aggressive gases |
| Degree of protection | IP54 |
| Ambient temperature | −15 °C to +70 °C |
| Electrical connection | Screw terminals, cable gland |
| Pressure connections | P1 (+) and P2 (−) for overpressure, negative pressure or differential pressure |
| Standard/approval | EN 1854, CE, UKCA, SIL (depending on version) |
Applications
- Gas flare systems
- Industrial burner systems
- Biogas and process plants
- Thermal oxidation
- Special plant construction
Suitability for your specific gas flare or burner system must be checked against the plant documentation and the manufacturer approvals.
Scope of delivery
For details of the supplied accessories and the exact device version, please contact us at service@c-nox.de. Please state article number 10089 and the type designation DUNGS LGW 50 – air pressure switch.
Technical data sheet
We will gladly send you the manufacturer’s technical data sheet or operating manual: Request data sheet.