Enclosed low-temperature gas flare NTV
18.230,80 € – 45.065,30 €
incl. VAT plus shipping costs
List price from per size · net ex works Neumünster · standard equipment without options
Prices apply to standard flares with 1 burner circuit – prices differ for additional burner circuits (up to 4) and options.
Illustration for reference only – the delivered flare may differ from the picture depending on size, burner circuits and selected options.
Enclosed low-temperature gas flare NTV — application and function
The NTV is the professional version of the C-nox low-temperature flares with enclosed combustion of biogas, sewage gas and synthesis gas at temperatures up to 850 °C – in 15 sizes from 400 to 6,000 kW.
Show more
C-nox flares feature a simple and robust design – keeping maintenance and operating costs to a minimum. Only high-quality components are used that meet all safety requirements (e.g. ATEX, DIN EN 298, ISO 22580).
Flame tube, burner and gas pipework made of stainless steel, base frame hot-dip galvanised, control cabinet made of GRP, prepared for condensate separator. Design basis: 55 vol.% CH₄, calorific value approx. 5.5 kWh/m³, gas pressure 25–100 mbar.
Illustration similar. List prices net plus VAT, ex works Neumünster, without options, freight and installation. Subject to technical changes.
Why a flare from C-nox?
- Direct from the manufacturer – design and manufacturing in Neumünster since 2006. References up to 30 MW in Germany, Sweden, Turkey and Mexico.
- Service from a single source – commissioning, maintenance, Maintenance contracts and Training by our own technicians.
- Spare parts available immediately – matching parts in our online shop, stock items in 1–3 working days.
- Transparent list prices per size, binding quotation once your gas data has been clarified.
Technical details
| Size | Gas flow [Nm³/h] | Capacity | DN | Total height |
|---|---|---|---|---|
| NTV 0.4 | approx. 30 – 70 | 400 kW | 40 | 5.5 m |
| NTV 0.8 | approx. 70 – 145 | 800 kW | 50 | 5.5 m |
| NTV 1.2 | approx. 100 – 220 | 1,200 kW | 65 | 5.5 m |
| NTV 1.6 | approx. 130 – 300 | 1,600 kW | 80 | 5.5 m |
| NTV 2.0 | approx. 165 – 365 | 2,000 kW | 80 | 5.5 m |
| NTV 2.4 | approx. 200 – 440 | 2,400 kW | 100 | 5.5 m |
| NTV 2.8 | approx. 240 – 510 | 2,800 kW | 100 | 5.5 m |
| NTV 3.2 | approx. 270 – 580 | 3,200 kW | 100 | 5.5 m |
| NTV 3.6 | approx. 320 – 655 | 3,600 kW | 100 (125) | 6 m |
| NTV 4.0 | approx. 350 – 725 | 4,000 kW | 125 | 6 m |
| NTV 4.4 | approx. 380 – 800 | 4,400 kW | 125 | 7 m |
| NTV 4.8 | approx. 420 – 870 | 4,800 kW | 125 (150) | 7 m |
| NTV 5.2 | approx. 460 – 945 | 5,200 kW | 125 (150) | 7 m |
| NTV 5.6 | approx. 500 – 1,020 | 5,600 kW | 125 (150) | 7 m |
| NTV 6.0 | approx. 530 – 1,100 | 6,000 kW | 150 | 7 m |
Features
- Enclosed combustion up to 850 °C
- Gas flow approx. 30 to 1,100 Nm³/h (single-stage, at 55 vol.% CH₄)
- Firing capacity 400 to 6,000 kW
- Gas connection DN 40 to DN 150
- Flame tube, burner and gas pipework made of stainless steel
- Base frame hot-dip galvanised
- Components according to ATEX, DIN EN 298, ISO 22580
- Design compliant with ISO, KAS and TA Luft
Optional versions
- Booster blower (compressor)
- Motorised valve, 2-stage (from size 1.2)
- Winter package with enclosure incl. front doors and electric heating
- Stainless steel control cabinet
- Mounting on foundation or container roof
- Multi-stage operation, separate burner circuits
- Bivalent applications (e.g. biogas and natural gas)
- Integration of a support gas burner
- PLC control and PLC connection
Biogas flare NTV – enclosed low-temperature gas flare from the manufacturer
The C-nox NTV is an enclosed gas flare (emergency flare) for biogas plants, wastewater treatment plants, landfills and biomethane plants. It burns surplus or unusable gas safely and with low odour – for example during CHP shutdown, maintenance, gas grid faults or overproduction. The flame stays hidden inside the flame tube; combustion runs at up to approx. 850 °C.
Applications
- Biogas plants (agriculture, bio-waste, energy crops)
- Wastewater treatment plants – sewage gas flare for digesters
- Landfills – landfill gas flare
- Biomethane and gas upgrading plants (off-gas, emergency operation)
- Synthesis gas and industrial gas applications
Your benefits
- 15 sizes from 400 kW to 6,000 kW – to suit every plant size
- Robust, low-maintenance stainless steel design, base frame hot-dip galvanised
- Safety technology according to ATEX, DIN EN 298 and ISO 22580
- Made in Neumünster, spare parts available immediately
- Commissioning, maintenance, service contracts and training by our own technicians
Which size do I need?
With our Flare Finder you can determine the right size in one minute from gas flow or CHP output, methane content and gas pressure – including whether a compressor is required. You will receive a binding quotation once your gas data has been clarified.
Frequently asked questions
Is an emergency flare mandatory for a biogas plant?
In Germany, biogas plants generally require an additional gas consumer for faults (e.g. TRAS 120, permit under the Federal Immission Control Act). The flare must be able to burn the maximum gas volume safely. Requirements in other countries vary – we will be happy to advise you.
Can I replace my old flare?
Ja. Wir prüfen Anschlüsse, Gasdruck und Steuerung Ihrer Anlage und liefern eine passende NTV oder LCN-O als Ersatz – auf Wunsch mit Montage.
Additional information
| Size | 0.4 – 400 kW – DN 40, 0.8 – 800 kW – DN 50, 1.2 – 1,200 kW – DN 65, 1.6 – 1,600 kW – DN 80, 2.0 – 2,000 kW – DN 80, 2.4 – 2,400 kW – DN 100, 2.8 – 2,800 kW – DN 100, 3.2 – 3,200 kW – DN 100, 3.6 – 3,600 kW – DN 100 (125), 4.0 – 4,000 kW – DN 125, 4.4 – 4,400 kW – DN 125, 4.8 – 4,800 kW – DN 125 (150), 5.2 – 5,200 kW – DN 125 (150), 5.6 – 5,600 kW – DN 125 (150), 6.0 – 6,000 kW – DN 150 |
|---|
Related products
-

High-temperature gas flare HTV
48.433,00 € – 99.484,00 €incl. VAT
plus shipping costs
Select options This product has multiple variants. The options may be chosen on the product page -

Open low-temperature gas flare LCN-O
16.410,10 € – 22.717,10 €incl. VAT
plus shipping costs
Select options This product has multiple variants. The options may be chosen on the product page

Spare parts for industrial
gas and flare technology.
CONTEC GmbH & Co. KG
Haberstraße 23
24537 Neumünster
Germany